SHC-001 | Mini cabinet for boiler room automation
- A ready-made solution for automation of heating and cooling stations
- Supports 2 heating and cooling circuits
- Intuitive 4.3 inch touch screen with remote access option
- Smart connectivity with Building Management Systems (CNS) and cloud services
- Includes 6 temperature sensors
System |
Supported elements |
| Management and control | 1 x LPC-3.GOT.112 4.3″ LCD PLC HMI touch screen, capacitive, Wifi, metal housing |
| Up to 2 mixing circuits | 2 x PT1000-1CH strap-on temperature sensor with housing for measuring the inlet and outlet water temperature 2 x Mixing valves 0..10V/0..20mA or ON/OFF 230VAC 2 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| Up to 2 heat sources | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 2 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A 2 x Heat source activation 230VAC/1A or dry contact 2 x Heat source fault volt-free contact |
| 1 hot storage tanks | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature |
| 1 domestic hot water tank | 1 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 1 x Obtočna črpalka 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| 2 temperature measurements | 1 x PT1000-2E surface-mounted outdoor temperature sensor PT1000, IP30 1 x PT1000-2 surface-mounted room temperature sensor PT1000, IP30 or digital inputs |
| Hydraulic separator | / |
| 1 diverting module | 2 x Relay output 230VAC/1A |
| 4 spare outputs | 2 x Relay output 2 x Triac output |
USER MANUAL
SHC-002 | Basic cabinet for boiler room automation
- A ready-made solution for the automation of heating and cooling stations
- Supports 3 heating and cooling circuits
- Intuitive 7 inch touchscreen with remote access capability
- Smart connectivity with Building Management Systems (CNS) and cloud services
- Includes 8 temperature sensors
System |
Supported elements |
| Management and control | 1 x LPC-3.GOT.012 7″ LCD PLK HMI touch screen, capacitive, WiFi, metal housing |
| Up to 3 mixing circuits | 6 x PT1000-1CH strap-on temperature sensor with housing for measuring the inlet and outlet water temperature 3 x Mixing valves 0..10V/0..20mA or ON/OFF 230VAC 3 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| Up to 2 heat sources | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 2 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A 2 x Heat source activation 230VAC/1A or dry contact 2 x Heat source fault volt-free contact |
| Up to 2 hot storage tanks | 4 x PT1000-1C immersion temperature sensoz PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature |
| 1 domestic hot water tank | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 1 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| 4 temperature measurements | 1 x PT1000-2E surface-mounted outdoor temperature sensor PT1000, IP30 3 x PT1000-2 surface-mounted room temperature sensor PT1000, IP30 or digital inputs |
| 1 hydraulic separator | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 1 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| 1 diverting module | 2 x Relay output 230VAC/1A |
| 4 spare outputs | 2 x Relay output 2 x Triac outputs |
USER MANUAL
SHC-E02 | Extension cabinet for boiler room automation
- Expansion cabinet for adding up to 2 additional heat sources and up to 3 additional heating and cooling circuits
- Expandable to support up to 12 mixing circuits and 6 heat sources.
- Includes 7 temperature sensors
System |
Supported elements |
| Management and control | Extension for the SHC-002 cabinet or a standalone unit in the boiler room with a separate display in the living areas |
| Up to 3 mixing circuits | 6 x PT1000-1CH strap-on temperature sensor with housing for measuring the inlet and outlet water temperature 3 x Mixing valve 0..10V/0..20mA or ON/OFF 230VAC 3 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| Up to 2 heat sources | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 2 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A 2 x Heat source activation 230VAC/1A or dry contact 2 x Heat source fault volt-free contact |
| Up to 2 hot storage tanks | 4 x PT1000-1C immersion temperature sensoz PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature |
| Up to 3 domestic hot water tanks | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 1 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| 4 temperature measurements | 1 x PT1000-2E surface-mounted outdoor temperature sensor PT1000, IP30 3 x PT1000-2 surface-mounted room temperature sensor PT1000, IP30 or digital inputs |
| 1 hydraulic separator | 2 x PT1000-1C immersion temperature sensor PT1000 or PT1000-1I immersion temperature sensor PT1000 for measuring water temperature 1 x Circulation pump 0..10V/0..20mA/PWM 24V/100Hz or 230VAC/1A |
| 1 diverting module | 2 x Relay output 230VAC/1A |
| 4 spare outputs | 2 x Relay output 2 x Triac outputs |
USER MANUAL